Place of Origin: | XI'AN CHINA |
---|---|
Brand Name: | HERONG ELECTRIC |
Certification: | ISO9001 |
Model Number: | BAM12.384-564-3W |
Minimum Order Quantity: | 1PC |
Price: | Negotiable |
Packaging Details: | Export standard packing |
Delivery Time: | 30 work days |
Payment Terms: | L/C, T/T, D/A, D/P, Western Union, MoneyGram |
Supply Ability: | 2000000KVAR/YEAR |
Rated Voltage: | 12.384KV | Rated Capacity: | 564kvar |
---|---|---|---|
Rated Current: | 26.29A | Rated Capacitance: | 11.71uF |
Rated Frequency: | 50Hz | Internal Fuse: | Yes |
Insulation Level: | 42/95KV | Number Of Phases: | Three-phase |
Capacitance Deviation: | -3%~+3% | Package: | Export Standard Packing |
High Light: | High Voltage Capacitor Bank 50Hz,Three Phase High Voltage Capacitor Bank,564 Kvar High Voltage Shunt Capacitor |
12.384KV 564 kVar Capacitor Bank High Voltage 50Hz Rated Frequency
1. Overview of 12.384KV 564kVar High Voltage Shunt Capacitor
High-voltage capacitors are mainly composed of lead-out porcelain bushings, capacitive element groups and shells. The shell is sealed and welded by thin steel plates, and the outlet porcelain sleeve is welded on the shell. The wiring terminal is led out from the outlet porcelain bushing. The capacitor element group (also called the core) in the shell is formed by connecting several capacitor elements. The capacitive element is made of capacitor paper, film-paper composite or pure film as the working medium, and aluminum platinum as the pole plate. In order to meet the withstand voltage requirements of capacitors of various voltage levels, capacitive elements can be connected in series or in parallel. The electric passenger component group of a single three-phase capacitor is connected into a triangle inside the shell. In high-voltage capacitors with a voltage of 10kV and below, each capacitive element is connected in series with a fuse, which serves as the internal short-circuit protection of the capacitor. Some capacitors are equipped with discharge resistance. When the capacitor is disconnected from the grid, it can be discharged through the discharge resistance. Generally, the residual voltage of the capacitor can be reduced to below 75V after 10 minutes.
2. Function of 12.384KV 564kVar High Voltage Shunt Capacitor
High voltage parallel capacitor is composed mainly of the packet, shell and insulation porcelain, the packet is connected in a particular way by dozens of components, separated by insulation and wrapped. The shell is welded with thin steel plate (or stainless steel plate),the two sides of the wall have the bracket for welding and installing. The lid of box is covered with (or embedded pressure assembly) line casing,components are made of polypropylene film and aluminum foil,and the capacitor is filled with excellent electrical insulation liquid impregnant.
Rated voltage |
12.384KV |
Rated frequency | 50Hz |
Rated Capacity | 564 kvar |
Insulation level | 42/95KV |
Internal fuse | Yes |
Number of phases | Three-phase |
Capacitance deviation | -3%~+5% |
Package | Export packing |
Loss tangent value (tanδ) | ≤0.0003 |
Discharge resistance | The capacitor is equipped with a discharging resistor. After being disconnected from the grid, the voltage on the terminal can drop below 50V within 5 minutes |
3. Main features of 12.384KV 564kVar High Voltage Shunt Capacitor
(1) In the transmission line, high-voltage capacitors can be used to form a series compensation station to improve the transmission capacity of the transmission line.
(2) In large-scale substations, high-voltage capacitors can be used to form a static phase-controlled reactor type dynamic reactive power compensation device (SVC) to improve power quality.
(3) At the end of the distribution line, the use of high-voltage capacitors can improve the power factor at the end of the line and ensure the voltage quality at the end of the line.
(4) High-voltage capacitors are installed in the middle and low-voltage bus sections of the substation to compensate for the reactive power consumed by the load and improve the power factor on the bus side.
(5) In load terminal stations with non-linear loads, high-voltage capacitors will also be installed for filtering.
4. Applicable standard of 12.384KV 564kVar High Voltage Shunt Capacitor
IEC60871 and equivalent standard
5. Working conditions of 12.384KV 564kVar High Voltage Shunt Capacitor
1, place of use: indoors or outdoors.
2 Altitude: ≤1000 m. (High altitude products can be designed according to user requirements)
3, ambient temperature: -40 ℃ ~ + 50 ℃.
4, the installation site should be free of harmful gases, no conductive or explosive dust.